Switch Specifications:
Electrical Configuration Matrix (Model 140/141)
|
|
|
|
|
|
|
A,B
|
Terminal Strip, 7 Position. Access for Conduit Hub or Cable Grip Connector
|
CE (Low Voltage)
|
NEMA 4X / IP 66 (Engineered Plastic)
|
Field Wireable. Separate junction box is not required. Externally adjustable switch set points.
|
|
C,D
|
1/2" Conduit, Flying Leads, 18 Awg
|
CSA / UL Class I, Division I, Groups C & D, Class II, Division I, Groups E,F & G
|
NEMA 7, with optional NEMA 4X
|
Explosion proof design. Externally adjustable switch set points.
|
|
E,F
|
1/2" Conduit, 7 Position Terminal Strip,
|
CE (Low Voltage), CSA /UL Div 2
|
NEMA 4X
|
Great Option for Hazardous Locations, Anodized Aluminum Enclosure
|
REED SWITCH RATINGS (Resistive Load)
|
|
|
|
|
Option:
|
B (Normally Open)
|
A
|
|
*Power
|
25 W
|
3W
|
|
Max. Current
|
0.5 Amps
|
0.25 Amps
|
|
Max. Voltage VAC/VDC
|
240
|
125
|
|
Setting ( %F.S.)
|
10 to 90
|
10 to 90
|
|
Hysteresis (Max/Nom)
|
15% / 8% (F.S.)
|
10% / 5% (F.S.)
|
|
Repeatability
|
1% F.S.
|
1% F.S.
|
* Product of the switching voltage and current shall not exceed the power rating of the device.